Isolation Room Concept
– A Turn Key Solution for hospitals
Isolation
room
WC
Ante
room
CLEAN AIR CONTAMINATED AIR AIR SUPPLY AIR EXHAUST
Air Balancing
Air balancing to be done on the VAV’s, to achieve a minimum of 2.5 Pa differential
pressure between the outside corridor (reference) and the inside of the room.
Contaminated air is cleaned through the Genano unit and exhausted out of the
building.
The only exhaust to be installed inside the room is the Genano unit.
• No exhaust diffusers
• Ceiling to be completely sealed (no tiles)
• Doors between the corridor and the room to be completely sealed